EKFG – Write command "Configuration of the system"

With this write command the FU will get the channels (analyzers) sending the current signals and their sequence. Furthermore the FU will get the channels that should be called with the total channel command "K0" or "KV Ln", i.e. the channels that shall be included to operation modes like measurement, zerogas and spangas. With the string XYZ the FU will be told which chemical component or virtual device (e.g. Lambda) shall be combined with which channel. The string XYZ will be for instance C0, N0, Nox or BRETT (Lambda according to Brettschneider) etc. The other physical or virtual channels can only be called directly with their channel number.

If no component and no channel number will be specified, the FU will get its default configuration of the system. That means, that all physical and virtual available components will be included to the read and control commands with the total channel command "K0" or "KV Ln". Besides, the TBCC can get the real physical composition of the FU with the read command "AKFG".

Write command

EKFG K0 XYZ Kn XYZ Km XYZ Kx

Adjusted channel x, component XYZ

Adjusted channel m, component XYZ

Adjusted channel n, component XYZ

Addressed channel 0

Code

EKFG KV Ln Kn ... Kx

Adjusted channel n to x

Lines getting assigned with adjusted channels

Addressed channel; front-end computer

Code

Response

EKFG 0

Error status

Code

2 - 90

AK

90003752(1) [AK-Commands] 10/98