Versatile Interface Board

Appendix C.2 VIB Installation and Configuration

Appendix C.2.1 VIB Installation

The VIB has been installed behind the service panel of the Liebert FS. The power/communications cable has been connected to the Main Control Module at the factory.

NOTE

If The VIB option has been purchased separately, refer to the installation instructions included with the kit for the proper mounting procedure.)

Figure 118 Versatile Interface Board mounted in the Liebert FS

Appendix C.2.2 VIB Requirements

The VIB requires software version 2.09 or later to operate properly. To verify the software version, press F6 from the main screen of the display panel. The software version is displayed in the lower left corner of the display. Press F6 when finished.

Appendix C.2.3 VIB Input Specifications

Opto-isolated inputs, active high.

Minimum Trigger Voltage: 3.5V DC (“IN” relative to “COM”).

Maximum Operating Voltage: 32V DC (“IN” relative to “COM”).

Minimum Input Current: 5mA DC.

Inputs must be present for at least 200ms to be recognized as valid signals.

Each input has a green status LED to indicate assertion of the signal.

Appendix C.2.4 VIB Output Specifications

Dry contact Form C relay: Normally Open (NO), Normally Closed (NC) and Common (COM) out- puts available.

Maximum Contact Resistance: 50mΩ

Minimum Insulation Resistance: 100MΩ at 500V DC

Maximum Switching Power: 500VA, 90W

Maximum Switching Voltage: 250V AC, 30V DC

Maximum Switching Current: 2A AC, 3A DC

Minimum Life: 100,000 operations on resistive loads

Each output has a green status LED to indicate assertion of the signal