Rosemount 2088 and 2090
Reference Manual
Figure
Load Limitations
LOAD (OHMS)
Max. Load = 45.4 (Power Supply Voltage)
1158
1000
800
600
400 |
|
|
|
|
|
|
| Operating |
|
|
| |
|
|
|
|
|
|
|
|
|
| |||
200 |
|
|
|
|
|
|
| Region |
|
|
| |
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |
0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| 30(1) |
|
| |
| 10.5 | 15 | 20 | 25 | 36 |
POWER SUPPLY (DC VOLTS)
(1) For CENLEC EX ia Approval, power supply must not exceed 30 volts.
NOTE
Minimum load impedance for Output Code N is 100 kilohms.
Field Wiring
All power to the transmitter is supplied over the signal wiring. Signal wiring need not be shielded, but use twisted pairs for best results. Do not run unshielded signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. For high EMI/RFI environments, shielded twisted pair cable should be used. To power the transmitter, connect the positive power lead to the terminal marked “PWR/COMM+” and the negative power lead to the terminal marked
To connect test equipment for monitoring the output of the Rosemount 2088 Smart during maintenance procedures, connect one lead to the terminal labeled “TEST+” and the other lead to the terminal labeled
Signal wiring may be grounded at any one point on the measurement loop, or it may be left ungrounded. The negative side of the power supply is a recommended grounding point. The transmitter case may be grounded or left ungrounded.
Conduit connections at the transmitter should be sealed to prevent moisture accumulating in the field terminal side of the transmitter housing. Also, install wiring with a drip loop with the bottom of the drip loop lower than the conduit connection of the transmitter housing.