Reference Manual
Rosemount 2088 and 2090
Figure
FAILURE MODE AND SECURITY JUMPERS
Failure Mode
Positive
Negative
Test
As part of normal operation, the Rosemount 2088/2090 Smart Pressure Transmitter continuously monitors its own operation. This automatic diagnostic routine is a timed series of checks repeated continuously. If the diagnostic routine detects a failure in the transmitter, the transmitter drives its output either below or above specific values depending on the position of the failure mode jumper or switch.
The values to which
Standard Operation
Linear output: 3.9 ≤ I ≤ 20.8 mA
Fail low: I ≤ 3.75 mA
Fail high: I ≥ 21.75 mA
Linear output: 3.8 ≤ I ≤ 20.8 mA
Fail low: I ≤ 3.6 mA
Fail high: 21.0 ≤ I ≤ 23.0 mA
To determine the failure mode configuration of your transmitter, review the failure mode options using a 275 HART Communicator.
NOTE
The failure mode configuration, whether standard or
Jumper Locations | Without a meter installed |
The failure mode alarm jumper is located on the front side of the electronics module just inside the electronics housing cover and is labeled ALARM (See Figure