Rosemount 2088 and 2090
Reference Manual
With a meter installed
Transmitter Security
The failure mode alarm jumper is located on the LCD faceplate in the electronics module side of the transmitter housing and is labeled ALARM (See Figure
After commissioning the transmitter, you may wish to protect the configuration data from unwarranted changes. The transmitter is equipped with a security jumper that can be positioned to prevent changes to the configuration data (see Figure
When the transmitter security jumper is in the “ON” position, the transmitter will not accept any “writes” to its memory. This means that configuration changes (such as digital trim and reranging) cannot take place when the transmitter security is on. To reposition the jumper, use the following procedure.
1.If the transmitter is installed, secure the loop, and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove the instrument cover in explosive atmospheres when the circuit is alive.
3.Reposition the jumper. Avoid contact with the leads and the terminals. Refer to Figure
4. Reattach the transmitter cover. The cover must be fully engaged to comply with
Figure | . |
and Security Jumper Locations |
|
Without LCD Meter | Low Power without LCD Display |
Alarm | Alarm |
|
Security
Security
With LCD Meter |
| Low Power with LCD Display |
|
| Security |
| Alarm | Alarm |
|
|
Security
2088A05A, 2088A05B
2088A05, 2088A05C