Sequence of Operation – Wall mounted thermostat mode

Note: While in Remote thermostat mode (see configuration), only the “FAN” and “TIME” buttons are acti- vated and will beep when pressed.

Memory Backup:

In the event of a power failure the control will retain all of it’s settings including the mode of operation. When power is restored, after a three minute time delay, the control will re- turn to the mode of operation that it was in prior to the power failure.

Fault conditions

Room air sensor fault: E01

If the room air sensor is disconnected, damaged or malfunctions the LCD display will flash error code “E01” to signify that a fault has occurred. Operation will con- tinue with the control using the last known value for the room air sensor.

Condensate fault: E02

If the control senses a condensate fault condition either through the optional con- densate pumps safety switch or the drain pan sensors, the LCD display will flash error code “E02”. The compressor will switch off for a minimum of three minutes and until the fault condition is corrected.

ID coil sensor fault: E03

The indoor coil sensor monitors the tem- perature of the indoor coil. If a freeze condition exists continuously for three minutes, the LCD will display error code “E03” to signify that a fault has occurred. The compressor will switch off for a mini- mum of three minutes and until the fault condition is corrected. Also, if the micro- processor detects an evaporator freeze condition four times within a 24 hour pe- riod, the filter check indicator will appear.

INFRARED Remote Control Option

Operational range 55- 90° F (in 1° increments.)

Figure 6

Pressing the “+” will increase the set point temperature setting. Pressing the “-“ button will de- crease the setpoint temperature setting.

Dry

Pressing the “DRY” button will place the unit in Dry Mode.

FAN

Pressing the “FAN” button will place the unit in fan mode.

HEAT

Pressing the “HEAT” button will place the unit in Heat mode.

COOL

Pressing the “COOL” button will place the unit in Cool mode.

Note: Batteries Included.

Power

Pressing the “POWER” button will turn the unit On or Off.

AUTO

Pressing the “AUTO” button will place the unit in Auto changeover mode.

FAN SPEED

Pressing the “FAN SPEED” but- ton will scroll the unit through fan the fan speed selection. The se- quence is High, Low and Auto.

Louver

Pressing the “LOUVER” button will enter the Louver Configura- tion mode. While in Louver Con- figuration mode, each successive press of the louver button will scroll through the louver positions. After idle for 10 seconds, the control will exit the Louver Configuration mode.

WLCA/WLHA High Wall Evaporator

25

www.enviromaster.com

Page 25
Image 25
EMI S1C, WLHA manual Memory Backup, Room air sensor fault E01, Condensate fault E02, ID coil sensor fault E03

WLHA, S1C specifications

The EMI S1C, also known as the WLHA, is a cutting-edge electronic device renowned for its advanced features and robust technologies. This innovative equipment caters to a wide range of applications, from multimedia processing to advanced communications. Its design showcases a seamless blend of functionality and performance, making it a preferred choice among professionals in various fields.

One of the standout characteristics of the EMI S1C is its high-performance processing capability. Equipped with a powerful multi-core processor, the device ensures rapid data processing and multitasking without compromising efficiency. This feature is particularly beneficial for applications requiring real-time data analysis and complex computational tasks.

The WLHA further distinguishes itself through its exceptional connectivity options. It supports multiple input and output standards, including USB, HDMI, and Ethernet, facilitating seamless integration with other devices. This flexibility allows users to connect a variety of peripherals and streamline workflows, enhancing overall productivity.

In terms of user experience, the EMI S1C places a strong emphasis on intuitive interaction. It features a user-friendly interface that simplifies navigation and accessibility. The touchscreen display provides responsive feedback, enabling users to operate the device effortlessly, even in high-pressure scenarios.

Another prominent aspect of the EMI S1C is its advanced power management system. The device is designed to optimize energy consumption without sacrificing performance. This sustainability feature is not only environmentally friendly but also crucial for mobile applications, where battery life is a significant consideration.

Furthermore, the WLHA's robust build quality ensures durability and resilience in diverse environments. The device is constructed with high-grade materials that withstand wear and tear, making it ideal for use in industrial settings or field operations where ruggedness is essential.

Security is also at the forefront of the EMI S1C's design. The device incorporates advanced encryption technologies and secure boot mechanisms to protect sensitive data from unauthorized access. This commitment to security is particularly relevant in today's digital landscape, where data breaches and cyber threats are prevalent.

In summary, the EMI S1C, WLHA is a versatile and powerful electronic device that excels in various domains. Its combination of high-performance processing, extensive connectivity, user-friendly interface, energy efficiency, durability, and robust security features makes it a top choice for professionals seeking reliability and innovation in their tools. Whether in multimedia, telecommunications, or industrial applications, the WLHA is poised to meet the demands of modern technology users effectively.