Empire Comfort Systems VFD42FB0L-1 Completion of Air Kit installation, Figure Figure, Page

Models: FD42FB2DF-1 VFD36FB2CL-1 VFD32FB0F-1 VFD36FB0F-1 VFD32FB0L-1 VFD42FB0F-1 VFD32FB2CL-1 VFD42FB2CL-1 VFD36FB2DL-1 VFD36FB2DF-1 VFD42FB0L-1 VFD36FB0L-1 VFD32FB2DF-1 VFD42FB2DL-1 VFD32FB2DL-1

1 20
Download 20 pages 19.36 Kb
Page 11
Image 11
Completion of Air Kit installation

OUTSIDE PLATE/VENT

SCREEN ASSEMBLYAIR DOOR Caulk and Install Duct Termination ASSEMBLY

OUTSIDE

HOOD

4” DIA. AIR DUCT CONNECTOR

(INSTALLER SUPPLIED) FIREBOX OR FIREPLACE

Figure 22

Completion of Air Kit installation

1.Determine the length of 4” Dia. rigid or flex duct connector (installer supplied) you will need from the firebox/fireplace to the exterior surface of the outside wall, where the air kit hood will be installed. Add a few extra inches to the length to allow for easier attachment of the outside duct connection prior to securing the outside rain cap hood to the building.

2.Secure the 4” dia. duct to the Air Door assembly collar on the firebox/fireplace with band clamps or screws.

3.Run the other end of the duct through the exterior wall cut- out.

4.From the outside of the building, connect the duct to the collar on the outside air vent assembly with band clamp or screws to secure.

5.Mate the outside rain cap hood over the air vent, seal with caulk as necessary, then secure with screws provided to the exterior wall surface. See Figure 22 and 23.

6.Figure 24 illustrates the various options for installation of the air duct run possibilities.

CAULKING

RAIN CAP

DUCT TERMINATION

WALL

Caulk and Install Duct Termination

Figure 23

Figure 24

23200-0-1206

Page 11

Page 11
Image 11
Empire Comfort Systems VFD42FB0L-1 Completion of Air Kit installation, Figure Figure, Caulk and Install Duct Termination