Clearances To Combustibles
TABLE 1: Minimum Clearances to Combustibles (Use Figure 1 on page 10 as a Guide)
Reflector Type | position |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard Reflector | A | 6” | 6” | 6” | 6” | 6” | 8” |
(Horizontal) | B | 30” | 36” | 36” | 36” | 36” | 36” |
| C | 55” | 55” | 74” | 87” | 87” | 87” |
| D | 30” | 36” | 36” | 36” | 36” | 36” |
|
|
|
|
|
|
|
|
45° Reflector Tilt | A | 12” | 18” | 18” | 18” | 18” | 18” |
| B | 30” | 36” | 36” | 36” | 36” | 36” |
| C | 55” | 55” | 74” | 87” | 87” | 87” |
| E | 36” | 36” | 36” | 36” | 36” | 36” |
| F | 60” | 60” | 60” | 60” | 60” | 60” |
|
|
|
|
|
|
|
|
A | 6” | 6” | 6” | 6” | 6” | 8” | |
(Horizontal) | B | 30” | 36” | 36” | 36” | 36” | 36” |
| C | 55” | 55” | 74” | 87” | 87” | 87” |
| D | 30” | 36” | 36” | 36” | 36” | 36” |
|
|
|
|
|
|
|
|
A | 12” | 18” | 18” | 18” | 18” | 18” | |
| B | 30” | 36” | 36” | 36” | 36” | 36” |
| C | 55” | 55” | 74” | 87” | 87” | 87” |
| F | 60” | 60” | 60” | 60” | 60” | 60” |
|
|
|
|
|
|
|
|
A | 12” | 18” | 18” | 18” | 18” | 18” | |
| B | 30” | 36” | 36” | 36” | 36” | 36” |
| C | 55” | 55” | 74” | 87” | 87” | 87” |
| E | 36” | 36” | 36” | 36” | 36” | 36” |
| F | 60” | 60” | 60” | 60” | 60” | 60” |
|
|
|
|
|
|
|
|
Unvented | Above A | 36” | 36” | 36” | 36” | 36” | 36” |
|
|
|
|
|
|
|
|
Warning:
Fire or explosion hazard
Can cause property damage, severe injury or death.
In all situations, clearances to combustibles must be maintained. Failure to observe clearances to combustibles may result in property damage, severe injury, or death.
Minimum clearances must be maintained from vehicles parked below the heater. Signs should be posted in storage areas to specify maximum stacking height to maintain required clearances to combustibles.
Caution should be used when running the system near combustible materials such as wood, paper, rubber, etc. Consideration should be given to partitions, storage racks, hoists, building construction, etc.
TABLE 1 gives minimum acceptable clearances to combustibles. Clearances as shown in TABLE 1 are not for use in
Enerco enerRadiant® XL Series Heater | 6 | Operating Instructions and Owner’s Manual |