Energy Tech Laboratories Modular Direct Fired Heaters Gas Connection Sizes, Gas Pressure Table

Models: Modular Direct Fired Heaters

1 28
Download 28 pages 34.52 Kb
Page 7
Image 7
Gas Connection Sizes
Gas Connection Diagram

Gas

Installation of gas piping must conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) – latest edition. In Canada, installation must be in accordance with CAN/CGA-B149.1 for natural gas units and CAN/CGA-B149.2 for propane units.

WARNING: INLET GAS PRESSURE MUST NOT EXCEED PRESSURE INDICATED ON NAMEPLATE. SEE UNIT NAMEPLATE FOR PROPER GAS SUPPLY PRESSURE AND GAS TYPE.

1.

Always disconnect power before working on or near a heater. Lock and tag the disconnect

 

switch or breaker to prevent accidental power up.

 

 

 

 

2.

Piping to the unit should conform with local and national requirements for type and volume of gas

 

handled, and pressure drop allowed in the line. Refer to the Gas Engineer’s Handbook for gas

 

line capacities.

 

 

 

 

3.

The incoming pipe near the heater should be sized to

 

Gas Connection Sizes

 

match the connection on the outside of the unit. Unit inlet

 

 

sizes are shown in the table to the right. Avoid multiple

 

Unit Size

 

Gas Pipe Size (NPT)

 

taps in the gas supply so the unit has a steady supply of

 

Size 1

 

¾”

 

gas at all times.

 

Size 2

 

1”

4.

Install a ground joint union with brass seat and a manual

 

 

 

 

 

Size 3

 

1”

 

shut-off valve external to the unit casing, as shown below,

 

 

 

 

 

 

Size 4

 

1-1/4”

 

adjacent to the unit for emergency shut-off and easy

 

 

 

 

Size 5

 

1-1/2”

 

servicing of controls.

 

 

 

 

 

 

 

5.

Provide a sediment trap, as shown below, before each

 

 

 

 

 

unit and where low spots in the pipe line cannot be avoided.

 

 

 

 

6.

Blow out the gas line to remove debris before making connections. Purge line to remove air

 

before attempting to start unit. Purging of air from gas lines should be performed as described in

 

ANSI Z223.1-latest edition “National Fuel Gas Code”, or in Canada in CAN/CGA-B149.

7.

All field gas piping must be pressure/leak tested prior to unit operation.

Use a non-corrosive

 

bubble forming solution or equivalent

 

 

 

 

 

for leak testing. The heater and its

Gas Pressure Table

 

individual shut-off valve must be

disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psi. The heater must be isolated from the gas supply piping system by closing its

Gas Pressure Type

Gas Pressure

Size 1-3 Inlet Pressure

7 in. w.c. – 14 in. w.c.

Size 4-5 Inlet Pressure

7 in. w.c. – 5 psi.

Max. Manifold Pressure - Natural Gas

5 in. w.c. maximum

Max. Manifold Pressure - Propane

2.5 in. w.c. maximum

individual manual shutoff valve

during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psi.

8. This unit requires a constant 7 in. w.c. minimum natural gas supply, when the unit is operating at maximum gas flow. If the gas supply exceeds 14 in. w.c. (5 psi. for sizes 4-5 housings) it will damage the internal valve components, and if it is below 7 in. w.c., the heater may not perform to specifications.

NOTICE

Refer to the heater rating plate for determining the

minimum gas supply pressure for obtaining the maximum gas capacity for which this heater is specified.

7

Page 7
Image 7
Energy Tech Laboratories Modular Direct Fired Heaters manual Gas Connection Sizes, Gas Pressure Table