Main Burner Adjustment
1. Once the pilot has been properly established, the manifold gas pressure or temperature rise should be adjusted to jobsite conditions. The gas pressure regulator (integral to the combination gas control on size
conditions. It is important that the gas be supplied to the burner in accordance with the input rating on the rating plate.
2. Create a high fire call for heat. This should be done with the blower on and all gas controls on. High fire can be achieved by removing the wire at terminal #4 (remove wires #2 and #4 for Maxitrol 44 systems) from the Maxitrol 14 amplifier.
3. The manifold pressure should be checked |
|
| Average Manifold Pressure vs. Firing Rate/Ft. of Burner |
| ||||
at the pressure tap downstream of the |
|
|
| |||||
| 6.00 |
|
|
|
|
|
| |
modulating valve. The graph to the right |
|
|
|
|
|
|
|
|
indicates the proper manifold pressure for |
| 5.00 |
|
|
|
|
|
|
the desired amount of BTUs per foot of | (in. w.c.) |
| Natural Gas | Propane Gas |
|
|
| |
burner. For natural gas systems, the high | 4.00 |
|
|
|
|
|
| |
|
|
|
|
|
|
| ||
fire manifold pressure should not exceed 5 | 3.00 |
|
|
|
|
|
| |
in. w.c. For propane gas, the high fire | Pressure |
|
|
|
|
|
| |
|
|
|
|
|
|
| ||
manifold pressure should not exceed 2.5 | 2.00 |
|
|
|
|
|
| |
in. w.c. Another method of checking high | Manifold |
|
|
|
|
|
|
|
fire is to measure the temperature rise of | 1.00 |
|
|
|
|
|
| |
the unit. The temperature rise should be |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
set to design conditions and typically is |
| 0.00 |
|
|
|
|
|
|
minimum 70°F. |
|
|
|
|
|
|
|
|
4. Remove the cap from the combination gas |
|
|
|
|
|
|
| |
| 0 | 100000 | 200000 | 300000 | 400000 | 500000 | 600000 | |
valve regulator adjustment (size |
|
| Firing Rate (BTU/Hr/Ft. of Burner) |
|
|
the cap from the MR212 valve (size
Using the regulator pressure adjusting screw, adjust the high fire manifold pressure to 5 in. w.c. maximum for natural gas and 2.5 in. w.c. maximum for propane gas. High fire should be set to generate the desired temperature rise. If the high fire screw is at the end of its adjustment and more pressure is needed, then adjust the main building gas pressure regulator spring (located external to the unit) to achieve the proper manifold pressure. Turning the regulator screw clockwise will increase pressure and
The high fire DC voltage should read 12 VDC minimum and should typically be 15 VDC on the Flame Safety Controller test jacks.
5.Reconnect the wire on the Maxitrol 14 amplifier at terminal #4 (wires #2 and #4 for Maxitrol 44).
6.The low fire manifold pressure must now be set. Low fire can be achieved
by removing the wire at terminal #5 from the Maxitrol 14 amplifier (remove #8 for Maxitrol 44). Check the low fire flame signal to ensure that the DC voltage is 12 VDC minimum on the Flame Safety Controller test jacks.
7.Using the bypass screw (located on the side of the M511 and M611 valves, and under the cap of the MR212 valve), adjust low the low fire manifold pressure until there is a very thin flame along the entire length of the burner. No dark spots should be seen in the burner. The burner may be observed through the
Maxitrol amplifier and gas components.
8. A final gas leak check shall be performed to verify the
11