3002503 11.06
| 1. Product Information |
| |
1.1 Function | |
Use | The EXHAUSTO RSIB Power Venter is intended for use as an |
| It can be installed |
| arrangements. It is specifically designed for applications requirinng efficient operation, low noise level, low |
| energy consumption, variable speed and compact design. The RSIB is for use with |
| and condensing appliances (Category I, II, III, IV) operating at flue gas temperatures at or below 575°F |
| (300° C). Typical uses include, but are not limited to, mechanical venting of gas and oil fired boilers and |
| water heaters and other appliances operating with discharge temperatures at or below 575°F (300° C). |
| The RSIB is for indoor and outdoor installations. |
Construction | The EXHAUSTO RSIB Power Venter is an efficient high temperature ventilator with a |
| cast aluminum impeller. The ventilator housing is made of corrosion resistant 316L stainless steel. It |
| is equipped with an |
| the air stream. A motor mounting plate on the front of the ventilator provides easy access to the inside |
| of the fan and the duct connections. The motor and impeller are mounted on the motor mounting |
| plate which is secured to the fan housing with six bolts. The stack connections are of the slip connection |
| type. The ventilator can be mounted on vibration insulated support legs or from ceiling mounting brackets. |
Listings | The RSIB model is tested and listed to UL378, Standard for Draft Equipment, UL705, Standard for Power |
| Venters, and |
| cover use with condensing appliances. This installation manual does not contain any system design |
| documentation. Please refer to the system design manuals or instructions by EXHAUSTO. The RSIB is a |
| component in the CASI, Chimney Automation System. |
Restrictions | The RSIB Power Venter should only be used with appliances operating on Natural Gas, |
| or fuel oil (#2 through #6). It should never be used with incinerators, incinerating toilets or solid- |
| fuel burning equipment. When used with multiple appliances and utilizing a Fan Speed Control or |
| a Variable Frequency Drive to control the fan speed, a barometric damper should be installed to prevent |
| overdraft conditions, unless the appliance(s) has a draft hood or a draft diverter. This limitation does |
| not apply when used with an EBC 12 or EBC 30, Pressure Control. The temperature of the flue gases |
| going through the Power Venter should never exceed 575°F (300°C). |
1.2 Components
Fig. 1
Outlet
Mounting
legs
Motor Mounting |
|
Plate | Mounting eyes |
Motor | and holes |
|