MOBILE HOME INSTALLATION
SPECIAL REQUIREMENTS: Pedestal models 1000 and 1600 are approved for mobile homes. All freestanding installation requirements on the preceding page plus the following must be met:
VENTING:
In Canada: Any
THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL, AND CEILING/ROOF MUST BE MAINTAINED.
OUTSIDE AIR :
Connection from the stoves air intake to the outside is mandatory,(MOBILE HOMES ONLY) either through a hole in the wall not higher than the stoves bottom, or through a hole in the floor beneath the pedestal using the fresh air adapter provided. If the air intake is through the floor, the hole in the pedestal back must be closed with the sheet metal cover provided. Avoid cutting any floor joists, wall studs, electrical wiring or plumbing. Seal around the outside air pipe with insulation to prevent drafts. Also install a 1/4” mesh rodent or pest screen in the end of fresh air pipe. Fresh air connection must be of a non combustible material (example: 4” 10.16 cm flexible aluminum single wall pipe.)
Fresh air could also be supplied from a vented crawlspace
The pedestal must be firmly bolted to the floor using 1/4” bolts. Be sure to replace any insulation or panels removed when fastening the bottom nuts.
If room air starvation occurs because the air intake is blocked with ice, leaves etc. Or because the stove door was left open, or due to a strong exhaust fan operating, dangerous fumes could be sucked into the room.
IN SOME AREAS IT MAY BE REQUIRED TO ELECTRICALLY GROUND THE STOVE.
When this unit is installed in a Mobile Home it must be grounded to the steel chassis or connected to a grounding rod.
Manufactured (Mobile) home installation must be in accordance with the Manufactured Home Construction and Safety Standard, UL 307B, Title 24 CFR, Part 3280 and/or The Standard for Manufactured Home Installations, ANSI A225.1/NFPA 501A
WARNING: DO NOT INSTALL IN A MOBILE HOME SLEEPING ROOM.
11