WEIGHT AND ELECTRICAL DATA • MQL
Motor/Drive Weight Data
MOTOR WEIGHTS
MOTOR TYPE |
|
|
|
| MOTOR HORSEPOWER |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| ||
1/3 | 1/2 | 3/4 | 1 | 1 1/2 | 2 | 3 | 5 | 7 1/2 | 10 | 15 | ||
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
ODP | 25 [11] | 28 [13] | 30 [762] | 35 [16] | 45 [20] | 35 [16] | 75 [34] | 100 [45] | 125 [57] | 125 [57] | 220 [100] | |
|
|
|
|
|
|
|
|
|
|
|
| |
TEFC | 28 [13] | 35 [16] | 33 [338] | 45 [20] | 65 [29] | 70 [32] | 85 [39] | 105 [48] | 145 [66] | 160 [73] | 295 [134] | |
|
|
|
|
|
|
|
|
|
|
|
| |
E+ | N/A | N/A | N/A | 40 [18] | 55 [25] | 55 [25] | 90 [41] | 100 [45] | 145 [66] | 130 [59] | 300 [136] | |
|
|
|
|
|
|
|
|
|
|
|
| |
2 SPEED | 45 [20] | 35 [16] | 33 [338] | 45 [20] | 40 [18] | 70 [32] | 75 [34] | N/A | N/A | N/A | N/A | |
|
|
|
|
|
|
|
|
|
|
|
|
NOTES:
1.Includes motor, pulleys, belts, and motor base.
2.Motor/drive weight data is shipping weight in pounds [kilograms].
Motor Electrical Data
|
|
| MAXIMUM MOTOR AMPERAGE |
|
| |||
HORSEPOWER |
|
|
|
|
|
|
| |
|
|
| VOLTAGE |
|
|
| ||
| 115/1 | 208/1 | 230/1 | 277/1 | 208/3 | 230/3 | 460/3 | 575/3 |
1/3 | 6.3 | 3.5 | 3.2 | 2.6 | 1.7 | 1.5 | 0.8 | - |
1/2 | 7.8 | 4.3 | 3.9 | 3.6 | 2.2 | 2.1 | 1.1 | 0.9 |
3/4 | 10.6 | 5.4 | 5.3 | 5.0 | 3.2 | 3.0 | 1.5 | 1.2 |
1 | 15.0 | 8.3 | 7.5 | 5.5 | 4.0 | 3.6 | 1.8 | 1.4 |
1 1/2 | - | - | - | - | 5.3 | 5.0 | 2.5 | 1.9 |
2 | - | - | - | - | 7.0 | 6.4 | 3.2 | 2.5 |
3 | - | - | - | - | 9.1 | 9.0 | 4.5 | 3.2 |
5 | - | - | - | - | 14.2 | 12.8 | 6.4 | 5.2 |
7 1/2 | - | - | - | - | 22.2 | 21.6 | 10.8 | 8.2 |
10 | - | - | - | - | 28.6 | 28.4 | 14.2 | 11.4 |
15 | - | - | - | - | 44.9 | 40.6 | 20.3 | 16.2 |
NOTES:
1.Actual motor nameplate AMPs may vary, but will not exceed values shown.
2.Consult factory for applications requiring special motors.
General Fan Notes
Forward Curved Fans (Belt Drive)
1.Consult factory for applications at operating conditions not in the following table and curves.
2.Fan motor voltage, fan rotation, and fan RPM may require field setting/adjustment.
3.Drive losses not included in fan performance table and curves.
4.In direction of airflow, after fan discharge – only LPM (Large Plenum) and EHB (Electric Heat Blow Thru) are available.
5.Section will have internal isolation.
Plug Fans (Direct Drive)
1.Consult factory for applications at operating conditions not in the following table and curves.
2.VFD's are recommended for operation and field balancing of units whether factory supplied and factory mounted, field supplied and factory mounted, or field supplied and field mounted.
3.In direction of airflow, there must be space prior to the plug fan inlet. For sizes 02 through 06, the minimum requirement is either an SAM (Small Access) or an MCM (Medium Coil). For sizes 08 through 17, the minimum requirement is an MAM (Medium Access).
4.Section will have internal isolation.
13 |