Electrical

NS SPLIT INSTALLATION MANUAL

Electrical

General

Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable. See unit electri- cal data for fuse or cicuit breaker sizing information.

Electrical Data

 

Rated

Voltage

Compressor

HWA

Ext

Total

Min

Max

Model

Voltage

Min/Max

 

 

 

Pump

Loop

Unit

Circ

Fuse/

 

 

 

MCC

RLA

LRA

FLA

FLA

FLA

Amp

HACR

 

 

 

 

 

 

 

 

 

 

 

026

208-230/60/1

197/253

16.0

10.2

52.0

0.4

5.4

16.0

18.6

25

038

208-230/60/1

197/253

26.0

16.6

82.0

0.4

5.4

22.4

26.6

40

 

 

 

 

 

 

 

 

 

 

 

049

208-230/60/1

197/253

33.0

21.1

96.0

0.4

5.4

26.9

32.2

50

064

208-230/60/1

197/253

40.0

25.6

118.0

0.4

5.4

31.4

37.8

60

072

208-230/60/1

197/253

42.5

27.2

150.0

0.4

5.4

33.0

39.8

60

 

 

 

 

 

 

 

 

 

 

 

Rated Voltage of 208-230/60/1.

 

 

 

 

 

 

 

Rev.: 02/20/07

HACR circuit breaker in USA only.

 

 

 

 

 

 

 

 

Min/Max Voltage of 197/253.

 

 

 

 

 

 

 

 

 

All fuses Class RK-5.

 

 

 

 

 

 

 

 

 

Thermostat Wiring

Figure 12a: Thermostat Wiring

 

 

Thermostat

 

 

 

Y1

1st Stage Compressor

 

 

 

 

 

Y2

 

 

 

 

2nd Stage Compressor

 

 

O

Reversing Valve

 

 

 

Air Handler

 

L

Fault Signal

 

 

 

C

Common

C

Common

 

 

 

R

24 VAC

R

24 VAC

 

 

W

 

W

 

G

Fan

G

 

 

 

 

Air Handler transformer must be at least 75 VA.

Figure 12b: Thermostat Wiring for Dual Fuel Applications

Envision Split

 

 

Thermostat

 

Envision Split

 

 

 

Y1

1st Stage Compressor

 

Y1

 

 

 

Y1

 

 

 

 

 

 

 

Y2

2nd Stage Compressor

 

 

 

 

 

Y2

Y2

 

 

 

 

 

 

 

O

Reversing Valve

 

 

 

 

 

O

O

 

 

 

 

Fossil Fuel

 

 

 

 

P1

 

L

Fault Signal

P1

Furnace

 

 

 

 

 

 

 

LO

Lo

 

 

 

 

 

 

 

 

 

 

C

Common

C

Common

 

 

 

 

C

C

 

 

 

 

 

 

 

 

 

 

R

24 VAC

R

24 VAC

 

 

 

 

R

R

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

Auxiliary Heat Relay

 

 

Shut

 

 

 

 

 

 

G

Fan

G

 

P2

 

 

 

Auxiliary

Down

 

 

 

 

 

 

 

 

 

 

 

 

W

Heat Relay

 

 

 

 

 

 

Auxiliary Heat Relay

Note: Field installed DPST dual fuel relay

(Required for dual fuel installation)

General = chassis

Page 9
Image 9