Heat Recovery Connections

NS SPLIT INSTALLATION MANUAL

Heat Recovery Connections

To maximize the benefits of the heat recovery a minimum 50-gallon water heater is recommended. For higher demand applications, use an 80-gallon water heater or two 50-gallon water heaters connected in a series as shown below. Electric water heaters are recommended. Make sure all local electrical and plumbing codes are followed when installing a heat recovery.

Note: Under certain conditions, Envision dual capacity units operate with very low refrigerant discharge temperatures, producing little or no water heating capability. This scenario occurs when the unit is operating with cold entering source water (loop or well). Allowing the pump to operate during these conditions actually removes heat from the DHW cir- culating through the unit. To overcome this, Envision unit microprocessors have been programmed to disengage the desuperheater pump during such conditions. (During low capacity cooling operation, the pump will operate only if the DHW temperature entering the unit is less than the liquid line temperature plus 35º F. During high capacity cooling op- eration, the pump will operate only if the DHW temperature is less than the liquid line temperature plus 60º F.) Using a preheat tank, as shown in Figure 11, will maximize desuperheater capabilities.

Water Tank Preparation

To install a unit with desuperheater, follow these installation guidelines.

1.Turn off the power to the water heater.

2.Attach a water hose to the water tank drain connection and run the other end of the hose to an open drain or outdoors.

3.Close the cold water inlet valve to the water heater tank.

4.Drain the tank by opening the valve on the bottom of the tank, then open the pressure relief valve or hot water faucet.

5.Flush the tank by opening the cold water inlet valve to the water heater to free the tank of sediments. Close when draining water is clear.

6.Disconnect the garden hose and remove the drain valve from the water heater.

7.Refer to Plumbing Installation and Desuperheater Startup on page 14.

CAUTION: Elements will burn out if energized dry.

13