Envision Peripherals Series installation manual Refrigeration, Connection to Air Coil

Models: Series

1 36
Download 36 pages 34.9 Kb
Page 22
Image 22
Refrigeration

NS SPLIT INSTALLATION MANUAL

Refrigeration

The Envision series comes with a holding charge. The charge must be adjusted in the field based on performance. Refrigeration piping on the split consists of installing a brazed copper line set between the blower coil unit and the unit’s split compressor section. To select the proper tube diameters for the installation, refer to the table on page 9. Line sets over 60 feet long are not recommended because of oil return and pressure drop problems. The suction line must always be insu- lated. Handle and route the line sets carefully to avoid kinking or bending the tubes. If the line set is kinked or distorted and it cannot be formed back into its original shape, the bad portion of the pipe should be replaced. A restricted line set will affect the performance of the system.

Connection to Air Coil

Figures 1 and 2 illustrate typical Envision Split installations. The table on page 9 shows typical lineset diameters and maximum length. As in all R-410A equipment, a reversible liquid line filter drier is required to insure all moisture is removed from the system. This drier should be replaced whenever “breaking into” the system for service. All linesets should be insulated with a minimum of 1/2” closed cell insulation. All insulation should be painted with UV resistant paint or covering to insure long insulation life.

Fasten the copper line set to the blower coil unit as instructed by the coil installation instructions shown in Figure 14. Nitrogen should be bled through the system at 2 to 3 PSI to prevent oxidation inside the refrigerant tubing. Use a low silver phos-copper braze alloy on all brazed connections.

Braze line set to the service valve stubs on the inside front of the split cabinet as shown in Figure

Figure 13: Typical Split System Refrigerant Line Connections

13. Nitrogen should be bled through the system at

2 to 3 PSI to prevent oxidation contamination. Use

a low silver phos-copper braze alloy on all brazed

Service ports for attaching refrigerant gauges

Insulated

connections. Envision split units are shipped with

a factory charge and service valves are not to be

opened until the line set has been leak tested,

purged and evacuated. Schrader cores should be

removed before brazing. A heat sink should be used

on the service valves and TXV to prevent damage

caused by excessive heat.

Suction Line

Replace caps after

ccw

 

opening system

 

ccw

Braze

Connection

Liquid

Line

20

Page 22
Image 22
Envision Peripherals Series installation manual Refrigeration, Connection to Air Coil