NS SPLIT INSTALLATION MANUAL
Heat Recovery Unit for Domestic Hot Water
Service valves have been provided inside the unit for connecting the discharge gas line to a water heating heat recov- ery unit (see figure 5). To make the connections, close the service valves inside the unit by turning clockwise. Using a recovery canister connect to either of the schrader ports on the DSH service valves and recover the small amount of refrig- erant trapped inside of the
IMPORTANT - Reopen discharge line service valves before starting up unit, but only after leak checking, purging, and evacuating new discharge line.
Figure 5: Service Valves for Heat Recovery Unit Connections
To
Compressor
Heat Recovery
Unit “In”
From
Heat Recovery
Unit “Out” to
Reversing
Valve
Maximum
SIZE | 1/2” OD | 5/8” OD | 3/4” OD |
|
|
|
|
026 - 038 | Up to 9 ft. | Up to 25 ft. | Up to 30 ft. |
|
|
|
|
049 | Up to 5 ft. | Up to 13 ft. | Up to 30 ft. |
|
|
|
|
064 | N/A | Up to 9 ft. | Up to 25 ft. |
|
|
|
|
072 | N/A | Up to 6 ft. | Up to 20 ft. |
|
|
|
|
Figure 6: Typical Hot Water Piping Layout
| Cold | Hot |
Line set |
|
|
To Hot Water | Venting |
|
Generator |
| |
| Waste Valve or |
|
| Vent Coupling |
|
| P/T Relief | |
| Valve |
Insulated Line set
With UV Paint
To Air handler
|
| |
Hot Water |
|
|
Generator with |
|
|
Internal Pump | Drain Valve | Pipe Tee |
12