Each Kooltronic Air Conditioner is engineered for performance and built for reliability. They are designed to require no routine maintenance other than the cleaning of ambient air filters. If your air conditioner should require warranty service, please contact Kooltronic. If you require service out of warranty, we have compiled a trouble-shooting chart to assist your service personnel. If additional assistance is required contact Kooltronic at (609) 466-3400.

Problem

Cause

Solution

Unit not Cooling

No Power

Check Power Source and

 

 

 

Electrical Connections

 

Loss of Refrigerant

 

Locate and repair leak

 

Evaporator or Condenser

Replace Motor, Capacitor or

 

Blower not operating

 

entire Assembly

 

Filter clogged

 

Clean or replace Filter

 

Clogged Evaporator or

Clean Coil

 

Condenser Coil

 

 

 

Low Temperature Control

Check sensor wire connections

 

sensor wires broken

 

 

 

Low Temperature Control

Replace Thermostat or Relay

 

(Thermostat) defective

 

when applicable

 

Failed Compressor

Replace Compressor

 

 

 

Ice on Evaporator Coil

Insufficient Heat Load or Unit

Contact Kooltronic

 

Oversized for Application

 

 

 

Failed Evaporator Blower

Replace Evaporator Blower

 

 

 

Motor or Assembly

 

Clogged Evaporator Coil

Clean Coil

 

 

 

Condensate draining

Enclosure not properly sealed

Check and seal all openings

continuously

 

 

 

 

 

 

 

 

Excessive opening of Enclosure

Eliminate the frequency of

 

 

 

door opening

 

 

 

Excessive vibration

Defective Motor in Blower

Replace Motor

 

 

 

 

 

Defective Wheel in Blower

Replace Wheel

 

 

 

 

 

Compressor Loose

Tighten Mounting Bolts

 

 

 

Compressor Inoperative

Low line Voltage

Check Nameplate Voltage

 

 

 

against supply

 

 

 

 

 

Loss of Compressor Oil

Replace Compressor

 

 

 

 

 

Loss of Refrigerant

Locate and repair leak

 

 

 

 

 

Failed Compressor Capacitor

Replace Capacitor

 

 

 

 

 

Thermal Overload

Contact Kooltronic

 

 

 

 

 

Power interruptions

Allow Compressor time to reset

 

 

 

Refrigerant or Oil leaks

Crack or pin hole in tubing or

Replace tubing or rebraze joint

 

brazed joint

 

Condensate on the outside

Insufficient Heat Load or Unit

Contact Kooltronic

surface of the Enclosure

oversized for application

 