2.1.12 Programming
To enter programming mode, press and hold the EDIT button and while holding it, press the INFO button. The display shows a message describing the current parameter followed by the parameter‘s value. While in programming mode, the buttons have the following functions:
STOP: Exit programming mode and save all parameters
=: Shift position of parameter being edited
EDIT: Change value of current position of parameter being edited
INFO: Change parameter to edit
Some of the parameters may be locked out in the programming mode. If a parameter is locked, the parameter is displayed along with the current value and a lock is displayed on the left side of the display. The parameter can not be changed. Refer to jumper settings section for information on locking out parameters. The following parameters are available for editing:
PARAMETER | MESSAGE | RANGE |
BS | BATTERY AH SIZE | |
VR | BATTERY VOLTAGE | |
SR | SHUNT RATING | |
AS | AUTO START MODE | |
|
|
|
CR | CABLE RESISTANCE | |
SA | START A/100AH | |
TP | 80% TRIP POINT | |
FA | FINISH A/100AH | |
FV | FINISH VOLTAGE | |
CV | CUTOFF VOLTAGE | |
ST | 80% TIMEOUT | |
|
|
|
FT | CHARGE TIMEOUT | |
|
|
|
MP | MAX POWER RATING | |
CF | CHARGE FACTOR | |
|
|
|
DS | DELAY START TIME | |
CT | COOL DOWN TIME | |
CU | DVDT PERIODS | |
|
|
|
EM | EQUALIZE MODE | |
|
|
|
EI | EQUALIZE A/100AH | |
ET | EQUALIZE TIME | |
EC | EQUALIZE CYCLES | |
N1 | F1 FAULT DISABLE | |
N3 | F3 FAULT DISABLE | |
N4 | F4 FAULT DISABLE | |
N6 | F6 FAULT DISABLE | |
N7 | F7 FAULT DISABLE | |
AR | REFRESH TIME |
NOTES
A setting of 0 enables current sensor operation
0:Manual Start
1:
2:Auto Start (restart on AC power)
Exceeding this voltage terminates the charge immediately. Exceeding this time results in an F1 if F1 is enabled and ends normally if F1 is disabled. (see N1 parameter)
Exceeding this time results in an F7 if F7 is enabled and ends normally if F7 is disabled. (see N7 parameter)
*DO NOT EXCEED RATING OF CHARGER
Maximum return based on battery AH size. Setting this to 0 disables the charge factor.
Each period is 5 minutes. Setting this to 0 causes the charge to terminate when the trip point is reached. (opportunity charge)
0:Equalize disabled
1:Normal equalize
Setting this to 0 disables automatic equalize.
0:Enabled, 1: Disabled
0:Enabled, 1: Disabled
0:Enabled, 1: Disabled
0:Enabled, 1: Disabled
0:Enabled, 1: Disabled
Setting this to 0:00 disables automatic refresh.