3F110 Web Interface

3.3.4Channel 2, Channel 3 and Channel 4

The Channel 2, Channel 3 and Channel 4 tabs are used to configure sensor labels and to set temperature thresholds, temperature/humidity thresholds and/or alarm states for the sensors connected to sensor channels 2, 3 and 4 on the front of the F110. Sensor labels can be up to 14 characters in length.

Depending on whether an external temperature / humidity sensor, external temperature sensor or any additional external sensor is plugged into the sensor channel, configuration of each specific channel may vary.

3.3.4.1 External Temperature/Humidity

High and low thresholds can be defined for each temperature/humidity sensor. If the current temperature and/or humidity rises above the high threshold or falls below the low threshold, an alert will be generated. When the temperature and/or humidity returns to a normal state, the alert will clear and a follow-up notification will be sent.

The temperature/humidity sensors can be calibrated, if necessary, by entering correction values in the Adjust field for each temperature/humidity sensor. Temperature corrections entered here can only be entered in degrees Celsius (i.e. °Celsius = [5/9]*[°Fahrenheit-32]). Humidity corrections are entered in percent (%) Relative Humidity. To adjust the temperature and/or humidity down, enter a minus (-) sign before the value (i.e. -5). All temperature alert thresholds must be entered in degrees Fahrenheit and all humidity alert thresholds must be entered in percent (%) Relative Humidity.

Field

High

Low

Adjust

Temperature Units

Fahrenheit

Fahrenheit

Celsius

www.rletech.com

24

970.484.6510

Page 24
Image 24
Falcon F110 manual Channel 2, Channel 3 and Channel, External Temperature/Humidity