A P P E N D I X

MODBUS CONFIGURATION VIA TELNET

A.1. F110 Modbus Capabilities

By default, the F110 is enabled to listen on TCP port 502 for Modbus requests. The Modbus module can be enabled or disabled, the TCP port can be changed, and a list of IP addresses can be specified and used to either allow or deny Modbus requests.

A.2. Telnet Configuration

Modbus can be configured through the F110 Telnet interface. To open the Telnet interface, type the following on the command line being sure to replace <IP Address> with the IP address of the F110:

telnet <IP Address> 9999

Press Enter when prompted to enter Setup Mode. If Enter is not pressed within three (3) seconds, the connection will be closed automatically.

Figure A.1 Telnet Connection

Enter 2 and press Enter to select the SNMP/MODBUS Configuration option. At the next prompt, enter 2 and press Enter to select the MODBUS Configuration option. Follow the prompts below to configure Modbus on the F110.

www.rletech.com

29

970.484.6510

Page 29
Image 29
Falcon manual Modbus Configuration VIA Telnet, F110 Modbus Capabilities, Telnet Configuration