| Page 10 of 14 |
Appendix A. Advanced Topics
Appendix A.1. X30 Profibus LED indicators
LED 1 – Not used
LED 2 – Slave Online Status
Color | Frequency | Description | |
Green | - | Slave is online on the Profibus network | |
Off | - | Slave is not online on the Profibus network | |
LED 3 – Slave Offline Status |
| ||
|
|
| |
Color | Frequency | Description | |
Red | - | Slave is offline on the Profibus network | |
Off | - | Slave is not offline on the Profibus network | |
LED 4 – Fieldbus Diagnostics | |||
|
|
| |
Color | Frequency | Description | |
|
| Error in configuration: IN and/or OUT length set during | |
Red | 1 Hz | initialization of the Slave is not equal to the length set during | |
|
| configuration of the network. | |
|
| Error in User Parameter data: The length/contents of the | |
Red | 2 Hz | User Parameter data set during initialization of the Slave is | |
not equal to the length/contents set during configuration of | |||
|
| ||
|
| the network. | |
Red | 4 Hz | Error in initialization of the Profibus communication ASIC. | |
Off | - | No diagnostics present. |
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408)