Page 6 of 14 |
4.Configuring the FieldServer as a Profibus DP Server
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” filesprovided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Profibus DP Master.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Profibus communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual Node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
4.1.Profibus Settings
Section Title |
|
|
Bridge |
|
|
Column Title | Function | Legal Values |
System_Station_Address* | Profibus Station Address of the FieldServer |
Note:
The Profibus Station Address can also be set via the two rotary switches on the side of the FieldServer in which case the System_Station_Address setting must be omitted from the configuration file. The settings specified in the configuration file will override the settings on these switches.
Example
// Bridge
Bridge |
|
|
|
Title, |
| System_Station_Address |
|
Profibus DP, | 5 |
|