FS-8700-113 X30 Profibus DP Slave Driver Manual

Page 11 of 14

Appendix A.2. Setting the FieldServer’s Profibus Station Address

The Station Address can be set in the FieldServer’s CSV file using the

System_Station_Address, (refer to Section 4.1), or it can be set with the two rotary switches as indicated on the connection diagram. The left switch selects the left decimal digit and the right switch the right decimal digit of the Station Address.

Note that the software setting with the System_Station_Address overrides the hardware setting with the rotary switches.

Appendix A.3. Understanding Driver Communication Statistics

When connecting with Ruinet to the FieldServer, there are communication statistics displayed on the Connection, Node and Map descriptor screens for the Profibus DP driver.

The Transmit (Tx) message count indicates the number of times the driver wrote output data into the Profibus hardware card’s output buffers for transmission on the Profibus network. It does not indicate the actual number of transmissions on the Profibus network.

The Receive (Rx) message count indicates the number of times the driver read input data from the Profibus hardware card’s input buffers. It does not indicate the number of actual messages received on the Profibus network.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Page 11
Image 11
FieldServer FS-8700-113 instruction manual Appendix A.3. Understanding Driver Communication Statistics