FS-8700-42_Spectronics Driver Manual

Page 10 of 15

5.Configuring the FieldServer as a Spectronics Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Spectronics Client.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Spectronics communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1.Server Side Connection Descriptors

 

Section Title

 

 

 

 

 

Connections

 

 

 

 

 

Column Title

 

Function

 

Legal Values

 

Port

 

Specify which port the device is connected

 

P1-P8, R1-R23

 

 

 

to the FieldServer

 

 

 

Baud*

 

Specify baud rate

 

110 – 115200 standard baud

 

 

 

rates only

 

 

 

 

 

 

Parity*

 

Specify parity

 

Even, Odd, None, Mark,

 

 

 

Space

 

 

 

 

 

 

Data_Bits*

 

Specify data bits

7, 8

 

Stop_Bits*

 

Specify stop bits

 

1 (Vendor limitation)

 

Protocol

 

Specify protocol used

Spectronics

 

Handshaking*

Specify hardware handshaking

RTS, RTS/CTS, None

Example

//Server Side Connections

Connections

Port,

Protocol,

Baud,

Parity,

Handshaking

P1,

Spectronics,

9600,

None,

None

3Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 10
Image 10
FieldServer FS-8700-42 Configuring the FieldServer as a Spectronics Server, Server Side Connection Descriptors