| Page 14 of 15 |
Appendix A.4. Connection to York Modbus Microgateway
If connecting the FieldServer to a York Modbus Microgateway, the Node_ID of the Microgateway is defined by the address DIP switches. If switch 4 is set to ‘On’ and the other switches are set to ‘off’ then Node_ID of the Microgateway is ‘247’, the parity is ‘Even’, and the stop bits are 1. Other Node_ID combinations can be found in the York Modbus Microgateway Installation Manual.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408)