The Upload Event and Error Messages

The event and its error messages

The following event occurs when the receiving Network Management Card completes using the .ini file to update its settings.

Configuration file upload complete, with number valid values

If a keyword, section name, or value is invalid, the upload by the receiving Management Card succeeds, an additional event text states the error.

Event text

Description

 

 

Configuration file warning: Invalid

A line with an invalid keyword or value is ignored.

keyword on line number.

 

Configuration file warning: Invalid value

 

on line number.

 

 

 

Configuration file warning: Invalid

If a section name is invalid, all keyword/value pairs in that section

section on line number.

are ignored.

 

 

Configuration file warning: Keyword

A keyword entered at the beginning of the file (i.e., before any

found outside of a section on line number.

section headings) is ignored.

 

 

Configuration file warning:

If the file is too large, an incomplete upload occurs. Reduce the

Configuration file exceeds maximum

size of the file, or divide it into two files, and try uploading again.

size.

 

 

 

Messages in config.ini

A device associated with the Management Card from which you download the config.ini file must be discovered successfully in order for its configuration to be included. If the device (such as a UPS) is not present or, for another reason, is not discovered, the config.ini file contains a message under the appropriate section name, instead of keywords and values. For example:

UPS not discovered

IEM not discovered

If you did not intend to export the configuration of the device as part of the .ini file import, ignore these messages.

Errors generated by overridden values

The Override keyword and its value will generate error messages in the event log when it blocks the exporting of values.

See “Contents of the .ini file” on page 79 for information about which values are overridden.

Because the overridden values are device-specific and not appropriate to export to other Management Cards, ignore these error messages. To prevent these error messages, you can delete the lines that contain the Override keyword and the lines that contain the values that they override. Do not delete or change the line containing the section heading.