Temperature and Humidity Page

Brief status

Click Temp & Humidity on the left navigation menu to display the name, alarm status, temperature, and humidity (if supported) for each sensor.

Detailed status and configuration

Click the name of a sensor for detailed alarm status or to configure its values:

Identification and alarm status.

Parameter

Description

 

 

Name

A name for this sensor. Maximum: 20 characters.

 

 

Location

This physical location of the sensor. Maximum: 20 characters.

 

 

Alarm

One of the following is displayed:

Status

Normal if this sensor is not reporting an alarm condition.

 

• If this sensor is in an alarm state, the text of the alarm, indicating which threshold is violated,

 

and the severity of the alarm, indicated by color (red for critical, orange for warning).

 

 

Thresholds

See the next two sections for descriptions of the configurable thresholds and Hysteresis values.

 

 

Thresholds. For each sensor, you set the same types of thresholds for temperature and (if supported) humidity measured at the sensor.

Threshold

Description

 

 

Maximum

If the threshold for maximum temperature or for maximum humidity for the sensor is

 

exceeded, an alarm occurs.

 

 

High

If the threshold for high temperature or for high humidity for the sensor is exceeded, an alarm

 

occurs.

 

 

Low

If the temperature or humidity drops below its low threshold for the sensor, an alarm occurs.

 

 

Minimum

If the temperature or humidity drops below its minimum threshold for the sensor, an alarm

 

occurs.

 

 

Hysteresis. This value specifies how far past a threshold the temperature or humidity must return to clear a threshold violation.

For Maximum and High threshold violations, the clearing point is the threshold minus the hysteresis.

For Minimum and Low threshold violations, the clearing point is the threshold plus the hysteresis.

Increase the value for Temperature Hysteresis or Humidity Hysteresis to avoid multiple alarms if temperature or humidity that has caused a violation then wavers slightly up and down. If the hysteresis value is too low, such wavering can cause and clear a threshold violation repeatedly.