Output Relay Page

This option is only available for devices with installed Dry Contact I/O Accessories. Select the Environment tab, then Universal I/O from the top menu bar. Click Output Relay to display the status of the output relay and configure its values.

Parameter

Description

 

 

Name

A name for this output relay. Maximum: 20 characters.

 

 

Location

The location of this output relay. Maximum: 20 characters.

 

 

Alarm Status

Normal if this output relay is not reporting an alarm, or the severity of the alarm if this

 

output relay is reporting an alarm.

 

 

State

The current state of this output relay: Closed or Open.

 

 

Normal State

The normal (non-alarm) state of this output relay: Closed or Open.

 

 

Control

To change the current state of this output relay, check-mark the setting.

 

 

Delay

The number of seconds a selected alarm condition must exist before the output relay is

 

activated. Use this setting to avoid activating an alarm for brief transient conditions.

 

NOTE: Even if additional mapped alarms occur after the delay begins, the delay does not

 

restart but continues until the output relay is activated.

 

 

Hold

The minimum number of seconds the output relay remains activated after the alarm occurs.

 

Even if the activating alarm condition is corrected, the output relay remains activated until

 

this time period expires.

 

 