Schneider Electric AP9635 manual Identify up to four e-mail recipients

Models: AP9635

1 105
Download 105 pages 25.64 Kb
Page 77
Image 77

E-mail recipients.

Path: Administration>Notification>E-mail>recipients

Identify up to four e-mail recipients.

Setting

Description

 

 

To Address

The user and domain names of the recipient. To use e-mail for paging, use the e-mail address

 

for the recipient’s pager gateway account (for example, myacct100@skytel.com). The pager

 

gateway will generate the page.

 

To bypass the DNS lookup of the mail server’s IP address, use the IP address in brackets

 

instead of the e-mail domain name, e.g., use jsmith@[xxx.xxx.x.xxx] instead of

 

jsmith@company.com. This is useful when DNS lookups are not working correctly.

 

NOTE: The recipient’s pager must be able to use text-based messaging. The MGE Galaxy

 

300, MGE Galaxy 7000, Symmetra PX 250, and Symmetra PX 500 UPS devices do not

 

support paging.

 

 

E-mail

Enables (by default) or disables sending e-mail to the recipient.

Generation

 

 

 

SMTP Server

Select one of the following methods for routing e-mail:

 

Local: Through the Management Card’s SMTP server. This setting (recommended) ensures

 

that the e-mail is sent before the Management Card’s 20-second time-out, and, if necessary,

 

is retried several times. Also do one of the following:

 

• Enable forwarding at the Management Card’s SMTP server so that it can route e-mail to

 

external SMTP servers. Typically, SMTP servers are not configured to forward e-mail.

 

Check with the administrator of your SMTP server before changing its configuration to

 

allow forwarding.

 

• Set up a special e-mail account for the Management Card to forward e-mail to an external

 

mail account.

 

Recipient: Directly to the recipient’s SMTP server. With this setting, the Management Card

 

tries to send the e-mail only once. On a busy remote SMTP server, the time-out may prevent

 

some e-mail from being sent.

 

When the recipient uses the Management Card’s SMTP server, this setting has no effect.

 

 

Format

The long format contains Name, Location, Contact, IP address, serial number of the device,

 

date and time, event code, and event description. The short format provides only the event

 

description.

 

 

Language

Chose a language from the drop-down list and any mails will be sent in that language. It is

 

possible to use different languages for different users.

 

 

User Name

If your mail server requires authentication, type your user name and password here. This

Password

performs a simple authentication, not SSI.

Confirm

 

Password

 

 

 

E-mail test.

Path: Administration>Notification>E-mail>test

Send a test message to a configured recipient.

Network Management Card User’s Guide