FS-8700-42_Spectronics Driver Manual

Page 7 of 15

4.2.Client Side Connection Descriptors

 

Section Title

 

 

 

Connections

 

 

 

Column Title

Function

Legal Values

 

Port

Specify which port the device is connected

P1-P8, R1-R22

 

 

to the FieldServer

 

 

Baud*

Specify baud rate

110 – 115200, standard baud

 

rates only

 

 

 

 

Parity*

Specify parity

None (Vendor limitation)

 

Data_Bits*

Specify data bits

8 (Vendor limitation)

 

Stop_Bits*

Specify stop bits

1 (Vendor limitation)

 

Protocol

Specify protocol used

Spectronics

 

Handshaking*

Specify hardware handshaking

RTS, RTS/CTS, None

 

Poll Delay*

Time between internal polls

0-32000 s, 1 s

Example

//Client Side Connections

Connections

Port,

Protocol,

Baud,

Parity,

Handshaking,

Poll_Delay

P8,

Spectronics,

9600,

None,

None,

0.100s

4.3.Client Side Node Descriptors

 

Section Title

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

Column Title

 

Function

 

Legal Values

 

 

Node_Name

Provide name for node

 

Up to 32 alphanumeric

 

 

characters

 

 

 

 

 

 

Node_ID

 

Station address of physical server

1-255

 

 

 

node

 

 

 

 

 

 

 

 

Protocol

Specify protocol used

Spectronics

 

Port

 

Specify which port the device is

 

P1-P8, R1-R22

 

 

 

connected to the FieldServer

 

 

 

 

Example:

 

 

 

 

 

//Client Side Nodes

Nodes

 

 

 

Node_Name,

Node_ID,

Protocol,

Port

Spec_device1,

1,

Spectronics,

P8

2Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 7
Image 7
FieldServer FS-8700-42 instruction manual Client Side Connection Descriptors, Client Side Node Descriptors