| Page 7 of 15 |
4.2.Client Side Connection Descriptors
| Section Title |
|
|
| Connections |
|
|
| Column Title | Function | Legal Values |
| Port | Specify which port the device is connected | |
|
| to the FieldServer |
|
| Baud* | Specify baud rate | 110 – 115200, standard baud |
| rates only | ||
|
|
| |
| Parity* | Specify parity | None (Vendor limitation) |
| Data_Bits* | Specify data bits | 8 (Vendor limitation) |
| Stop_Bits* | Specify stop bits | 1 (Vendor limitation) |
| Protocol | Specify protocol used | Spectronics |
| Handshaking* | Specify hardware handshaking | RTS, RTS/CTS, None |
| Poll Delay* | Time between internal polls |
Example
//Client Side Connections
Connections
Port, | Protocol, | Baud, | Parity, | Handshaking, | Poll_Delay |
P8, | Spectronics, | 9600, | None, | None, | 0.100s |
4.3.Client Side Node Descriptors
| Section Title |
|
|
|
|
|
| Nodes |
|
|
|
|
|
| Column Title |
| Function |
| Legal Values |
|
| Node_Name | Provide name for node |
| Up to 32 alphanumeric | ||
|
| characters | ||||
|
|
|
|
| ||
| Node_ID |
| Station address of physical server |
| ||
|
| node |
| |||
|
|
|
|
|
| |
| Protocol | Specify protocol used | Spectronics | |||
| Port |
| Specify which port the device is |
| ||
|
|
| connected to the FieldServer |
|
|
|
| Example: |
|
|
|
|
|
//Client Side Nodes
Nodes |
|
|
|
Node_Name, | Node_ID, | Protocol, | Port |
Spec_device1, | 1, | Spectronics, | P8 |
2Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408)