FieldServer FS-8700-47 instruction manual Appendix A.18. Real Time Clock Synchronization, Datime

Models: FS-8700-47

1 51
Download 51 pages 5.35 Kb
Page 40
Image 40

FS-8700-47 DNP 3.0 Driver Manual

Page 40 of 51

 

 

Appendix A.18. Real Time Clock Synchronization

The FieldServer has a real time clock. ProtoCessors have a software clock. If using a ProtoCessor, it is advisable to update the clock on the device periodically.

Remote update of Real Time Clock – Server configuration

Regardless of the platform in use, it is possible to have the FieldServer set its clock using the DNP 3.0 protocol when the driver is configured as a Server. The following actions are required:

Configure the driver to perform remote updates (Node parameter ‘Real_Time_Clock_Control’ = ‘Update-from-Remote’.

Set update frequency (Connection parameter ‘RTC_Update_Rqst_Interval’, default -2000. Value is specified in milliseconds. )

Have the Client send the time using Object 50 variation 1 (Time & Date CTO: Absolute Time) to the Server. When the Server receives this time it will store the value in a Data Array, as well as use it to update the real time clock.

Example

//

Server Side Connections

 

 

Ports

 

 

 

port

,Baud

,Protocol

,RTC_Update_Rqst_Interval

P1

 

,2400

,DNP

,123

 

 

 

 

 

//

Server Side Nodes

 

 

 

Nodes

 

 

 

Node_Name

,Node_ID

,Protocol

,Real_Time_Clock_Control

Node_A

,11

,DNP

,Update-from-Remote

 

 

 

 

 

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name ,Data_Array_Name ,Data_Array_Offset

,Function

,Node_Name

,Address

,Length

,dnpDataType

,dnpDataVari

Store_Time

,DA_TIME

,0

,Server

,Node_A

,0

,50

,50

,1

In this example, the Server has been configured to request a time update every 123 milliseconds and the request will be made by notifying the remote device that an update is required. The Server does this by setting a flag in the response internal indications bits. The default update is 2 seconds. If using the default, omit the specification of the ‘RTC_Update_Rqst_Interval’ parameter.

Remote update of Real Time Clock – Client configuration

If using the DNP 3.0 driver as a Client and you want to configure the driver to respond to Server requests for real time clock updates then:

Create a Data Array named ‘DNP3_RTC_NODEx’ where x is the Server node station address. The format for the Data Array should be UINT32.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com