5.Configuring the FieldServer as a DNP 3.0 Driver Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files provided with the FieldServer.)

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a DNP 3.0 Driver Client.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for DNP 3.0 Driver communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1.Server Side Connection Descriptors

 

Section Title

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

Column Title

 

 

 

Function

Legal Values

 

Port

 

Specify which port the device is connected to the

P1-P8, R1-R22

 

 

 

FieldServer

 

 

 

 

 

Baud*

 

Specify baud rate

 

 

110 – 115200, standard baud

 

 

 

 

rates only

 

 

 

 

 

 

 

 

 

Parity*

 

Specify parity

 

 

 

Even, Odd, None, Mark, Space

 

Data_Bits*

 

Specify data bits

 

 

7, 8

 

 

 

 

 

 

 

 

 

 

Stop_Bits*

 

Specify stop bits

 

 

1

 

 

 

 

 

 

 

 

 

 

Protocol

 

Specify protocol used

 

 

DNP

 

 

 

 

 

 

 

 

 

 

Handshaking*

 

Specify hardware handshaking

None

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

// Server Side Connections

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

Port

,Baud

,Parity

,Protocol

,Handshaking

 

 

 

P8

,9600

,None

,DNP

,None

 

 

2Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.