Configuration

Cfg AC Limits (Configure AC Limits)

Cfg AC Limits is a sub-menu. If selected, a list of sub-menu items appear. For more information on this sub menu, Configure AC Limits, see page 41.

Force Charge

Configurable setting This setting forces the charger to be enabled (On) whenever you have re qualified AC. The default setting for Force Charge is On (enabled).

# Chg Stages

Full name Number of charge stages

Configurable setting These settings let you adjust your charger stages to either two-stage charging or three-stage charging. The default setting for

# Chg Stages is 3Stage. (“Battery Charging Reference” on page 55.)

# Chg Stages

[3Stage]

Eqz Volts

Full name Equalization voltage

Configurable setting This setting lets you set the desired equalization voltage. This menu is displayed only if charger equalization is enabled. Select a setting based on the battery manufacturer’s recommendation. For more information, see “Battery Charging Reference” on page 55.

Eqz Volts

[15.5V]

You can adjust Eqz Volts settings as follows:

Force Charge

[On]

When to use Turn Force Charge to On if you want to automatically start charging whenever you connect to a qualified AC input, regardless of whether the Charger is Enabled or Disabled.

Turn Force Charge to Off if you want charging to be determined only by whether the Charger is Enabled or Disabled.

Outcome If Force Charge is turned to On, the charger starts whenever you have qualified AC.

Range of values

Increment

Default

 

 

 

13.5 to 15.5 VDC

0.1 volts

15.5 VDC

 

 

 

40

Freedom SW 3000 Owner’s Guide

Page 54
Image 54