Specifications

All transfer specifications are at nominal conditions: ambient temperature of 77 °F (25 °C), 120 VAC, 60 Hz input, unless otherwise specified.

Transfer and General Specifications

Transfer time—utility to invert

20 ms

 

 

Minimum AC input voltage for

85 VAC RMS

transfer

 

 

 

Maximum AC input voltage

135 VAC RMS

for transfer

 

 

 

Minimum AC input frequency

55 Hz

for transfer

 

 

 

Maximum AC input frequency

65 Hz

for transfer

 

 

 

Cooling

Fan-cooled, temperature controlled.

 

 

Supported AC input types

Split phase (up to 30 amps per line)

 

Dual input (up to 30 amps per line)

 

 

Environmental Specifications

Nominal Ambient temperature

77 °F (25 °C)

 

 

Maximum Operating

140 °F (60 °C) See “Invert Power

Temperature

Derating versus Ambient Temperature”

 

on page 64.

 

 

Storage temperature range

–40 ° to 185 °F (–40 to 85 °C)

 

 

Humidity: Operation/Storage

95% RH, non-condensing

 

 

Regulatory Approvals

Safety

CSA C22.2 No. 107.1

 

UL 458

 

 

EMC

FCC Part 15B Class B

 

Industry Canada ICES-0003 Class B

 

 

Fan Operation

The internal cooling fans are automatic and temperature-controlled.

NOTE: This internal temperature of the inverter/charger may be caused by heat in the inverter/charger or by high ambient temperature.