Troubleshooting

Table 9 Fault Messages

Fault

 

 

 

 

Number

Message

Fault Type

Cause

Solution

 

 

 

 

 

F24

Inverter/Charger internal

Escalating Auto Fault.

AC Under Voltage

Service required.

 

failure. Service required.

Must occur 3 times in 60

Shutdown (Inverter AC

 

 

 

seconds before becoming a

output)

 

 

 

manual fault.

 

 

 

 

 

 

 

F29

AC Backfeed fault: Service

Manual

AC Backfeed Shutdown

Service required.

 

immediately.

 

 

 

 

 

 

 

 

F30

Unit is too cold and has

Manual

Battery Under Temperature

Clear the fault and attempt one restart. Try

 

shut down. See guide.

 

Fault

restart again when ambient temperature is

 

 

 

 

warmer or gently warm the battery.

 

 

 

 

 

F40

Internal fault. If fault

Manual

No IPC communication

Service required.

 

persists, call Customer

 

 

 

 

Support.

 

 

 

 

 

 

 

 

F41

Internal fault. Reset. If fault

Manual

Dead battery charger

Try restarting dead battery charging once.

 

persists, call Customer

 

timeout

Then check the condition of the battery

 

Support.

 

 

and replace if necessary.

 

 

 

 

 

F502

Watchdog reset error

Manual

Watchdog reset error

Service required.

 

 

 

 

 

F505

Controller fault

Manual

Controller fault

Service required.

 

 

 

 

 

F506

Wrong fault identifier

Manual

Wrong fault identifier

Service required.

 

 

 

 

 

F507

Wrong identifier

Manual

Wrong identifier

Service required.

 

 

 

 

 