Battery Charging Reference
Table 11 Battery Current Defaults
|
| Flooded |
|
|
Current |
| (or wet) | Gel | AGM |
|
|
|
|
|
IB | Bulk | 20% Ah | 20% Ah | 20% Ah |
| Current |
|
|
|
| (ADC) |
|
|
|
|
|
|
|
|
IH | Absorption | 2% Ah | 2% Ah | 2% Ah |
| Exit Current |
|
|
|
| (ADC) |
|
|
|
|
|
|
|
|
IE | Equalize | 10% Ah | NA | NA |
| Current |
|
|
|
| (ADC) |
|
|
|
|
|
|
|
|
IB | Bulk | 20% Ah | 20% Ah | 20% Ah |
| Current |
|
|
|
| (ADC) |
|
|
|
|
|
|
|
|
IH | Absorption | 2% Ah | 2% Ah | 2% Ah |
| Exit Current |
|
|
|
| (ADC) |
|
|
|
|
|
|
|
|
IE | Equalize | 10% Ah | NA | NA |
| Current |
|
|
|
| (ADC) |
|
|
|
|
|
|
|
|
Table 12 Battery Time Defaults
|
| Flooded |
|
|
Time |
| (or wet) | Gel | AGM |
|
|
|
|
|
ΔTA | Absorption | 6 | 6 | 6 |
| Timeout |
|
|
|
| (hours) |
|
|
|
|
|
|
|
|
ΔTCV | Constant | 1 | 1 | 1 |
| Voltage |
|
|
|
| Absorption |
|
|
|
| Timeout |
|
|
|
| (hours) |
|
|
|
|
|
|
|
|
ΔTF | Float | 7 | 7 | 7 |
| Timeout |
|
|
|
| (days) |
|
|
|
|
|
|
|
|
ΔTE | Equalize | 1 | NA | NA |
| Timeout |
|
|
|
| (hours) |
|
|
|
|
|
|
|
|
The numbers presented in these tables are base numbers only and will vary with factors such as temperature compensation and battery type.
IMPORTANT: The custom battery factory defaults are the same as for an AGM battery.
59 |