4.2.Client Side Connection Descriptors

 

Section Title

 

 

 

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

 

 

 

Column Title

 

 

Function

 

 

 

 

 

Legal Values

 

Port

 

 

Specify which port the device is connected to the

 

P1-P8, R1-R21

 

 

 

 

FieldServer

 

 

 

 

 

 

 

Baud*

 

 

Specify baud rate

 

 

 

 

110 – 115200, standard

 

 

 

 

 

 

 

baud rates only

 

 

 

 

 

 

 

 

 

 

 

 

Parity*

 

 

Specify parity

 

 

 

 

 

Even, Odd, None, Mark,

 

 

 

 

 

 

 

 

Space

 

 

 

 

 

 

 

 

 

 

 

 

Data_Bits*

 

 

Specify data bits

 

 

 

7, 8

 

 

 

 

 

 

 

 

 

 

 

 

Stop_Bits*

 

 

Specify stop bits

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

Protocol

 

 

Specify protocol used

 

 

 

DNP

 

 

 

 

 

 

 

 

 

 

 

 

 

Handshaking*

 

 

Specify hardware handshaking

 

 

 

None

 

Poll Delay*

 

 

Time between internal polls

 

 

 

0-32000 seconds, 1

 

 

 

 

 

 

second.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Versions of the driver prior to 1.02a used a different

 

 

 

 

 

 

method to calculate DA offset. Refer to Appendix A.16.

 

OriginalStyle,

 

Application*

 

 

 

 

 

 

 

 

 

NoLink,

 

 

 

 

It is also possible to use this parameter to control if link

 

OrigStyle-NoLink

 

 

 

 

resets are used/required. Refer to Appendix A.15.

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

// Client Side Connections

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

 

 

 

Port

,Baud

,Parity

,Protocol

,Handshaking

,Poll_Delay

 

 

 

 

R1

,9600

,None

,DNP

,None

,0.100s

 

 

 

4.3.Client Side Node Descriptors

 

Section Title

 

 

 

 

Nodes

 

 

 

 

Column Title

Function

 

Legal Values

 

Node_Name

Provide name for node

 

Up to 32 alphanumeric

 

 

characters

 

 

 

 

 

Node_ID

DNP 3.0 station address of physical Server

0-65535

 

 

node

 

 

 

Protocol

Specify protocol used

DNP

 

Port

Specify which port the device is connected to

 

P1-P8, R1-R21

 

 

the FieldServer

 

 

 

Example

 

 

 

//Client Side Nodes

Nodes

 

 

 

Node_Name

,Node_ID

,Protocol

,Port

PLC 1

,1

,DNP

,P1

1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.