FS-8700-60 Gardner Denver Manual

Page 9 of 11

4

Motor current4

amps

4.1.5.Map Descriptor Example 2 - Polling only specific data items

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

Gar_cmd,

Gar_data,

Scan_Interval

GD_MBA1,

DA_Hourmeter,

0,

RDBC,

Node_1,

Service_Data,

Hourmeter_total,

1.0s

GD_MBA2,

DA_Oper_Mode,

0,

RDBC,

Node_1,

Operating_Mode,

Oper_mode,

1.0s

GD_MBA3,

DA_Motor_Amps,

0,

RDBC,

Node_1,

Operating_Data,

Motor_current,

1.0s

Note the active Read Block Continuous map descriptor function responsible for polling the Controller.

The Gar_cmd is set to indicate Operating Data must be polled for.

The Gar_data field is set to

“Motor_current” indicating that only this data item will be stored.

4.1.6.Map Descriptor Example 3 - Polling all data and isolating specific data items

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

Gar_cmd,

Gar_data,

Scan_Interval

GD_MBA1,

DA_Service_Data,

0,

RDBC,

Node_1,

Service_Data,

All,

1.0s

GD_MBA2,

DA_Oilage,

0,

Passive_Client,

Node_1,

Service_Data,

Oilage,

-

GD_MBA3,

DA_Hourmeter,

0,

Passive_Client,

Node_1,

Service_Data,

Hourmeter_total,

-

GD_MBA4,

DA_Oper_Mode,

0,

RDBC,

Node_1,

Operating_Mode,

All,

1.0s

GD_MBA5,

DA_Oper_State,

0,

Passive_Client,

Node_1,

Operating_Mode,

Oper_state,

-

GD_MBA6,

DA_Oper_Data,

0,

RDBC,

Node_1,

Operating_Data,

All,

1.0s

GD_MBA7,

DA_Disch_Temp,

0,

Passive_Client,

Node_1,

Operating_Data,

Discharge_temp,

-

Note the use of the passive map descriptor function. This map descriptor does not poll but receives data from the active map descriptor since the Gar_cmd and Node_Name fields match.

Note, the Gar_cmd indicates polling for Operating data.

Note that a specific data item, “Discharge_temp” is isolated here by still using the same Gar_cmd as the active map descriptor.

4RS2000 V4.0X Controllers set this field to zero

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 11
Image 11
FieldServer FS-8700-60 Map Descriptor Example 2 Polling only specific data items, Node1 OperatingData Motorcurrent