FS-8700-60 Gardner Denver Manual

Page 8 of 11

4.1.4.Map Descriptor Example 1 – Polling all available Controller Data

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

Gar_cmd,

Gar_data,

Scan_Interval

GD_MBA1,

DA_Service_Data,

0,

RDBC,

Node_1,

Service_Data,

All,

1.0s

GD_MBA2,

DA_Oper_Mode,

0,

RDBC,

Node_1,

Operating_Mode,

All,

1.0s

GD_MBA3,

DA_Oper_Data,

0,

RDBC,

Node_1,

Operating_Data,

All,

1.0s

Note the active Read Block Continuous map descriptor function responsible for polling the Controller.

The Gar_cmd field indicates the poll is for Operating Data.

The Gar_data field is set to “All” indicating that all available data is polled for.

Data will be stored as follows:

Offset

Description

Units

 

DA_Service_Data

 

0

Advisories

see ES/RS2000 Controller spec

1-20

10x (Shutdown code / Hourmeter reading) pairs

see ES/RS2000 Controller spec

21

Current total runtime hourmeter reading

Hours

22

Current loaded runtime hourmeter reading

Hours

23-28

6x Current temp hourmeters [H1] – [H6]

Hours

29-34

6x Stored temp hourmeters [OH1] – [OH6]

Hours

35

Last maintenance A

Hours

36

Last maintenance B

Hours

37

Oilage

Unknown, see ES/RS2000 controller spec

 

 

Operating mode data

0

Operating mode indication

 

see ES/RS2000 Controller spec

1

Sequence number2

 

see ES/RS2000 Controller spec

2

Unit operating state3

 

see ES/RS2000 Controller spec

 

 

Operating data

0

System pressure

 

divide by 16 for pressure in psig

1

Filter pressure

 

divide by 16 for pressure in psig

2

Discharge temperature

 

divide by 16 for temperature in degrees F

3

Reservoir temperature

 

divide by 16 for temperature in degrees F

2ES V2.0X Controllers do not respond with this field

3ES V2.0X Controllers do not respond with this field

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 10
Image 10
FieldServer FS-8700-60 instruction manual Data will be stored as follows