FS-8700-60 Gardner Denver Manual

Page 7 of 11

4.1.2.Driver Related Map Descriptor Parameters

Column

 

Function

 

 

Legal Values

 

Title

 

 

 

 

 

 

 

 

 

 

Node_Name

 

Name of Node to fetch data

 

One of the node names specified

 

from

 

in “Client Node Descriptor” above

Gar_cmd

Data poll commands

 

Service_Data, Operating_Mode,

 

Operating_Data

 

 

 

 

 

 

 

 

 

 

Available with Service_Data: All,

 

 

 

 

 

Advisories, Shutdown_codes,

 

 

 

 

 

Hourmeter_shutdown,

 

 

 

 

 

Hourmeter_total,

 

 

 

 

 

Hourmeter_loaded,

 

 

Data fields in a data poll

 

Hourmeter_temp,

 

 

 

Hourmeter_tmp_st, Last_maint_A,

 

 

command response

 

 

 

 

Last_maint_B, Oilage

Gar_data

 

message. Can be used to

 

 

 

 

 

 

poll for all or specific data

 

Available with Operating_Mode:

 

 

 

 

 

or just isolate specific items

 

 

 

 

All, Oper_mode, Seq_number,

 

 

in a “All” poll.

 

 

 

 

Oper_state

 

 

 

 

 

 

 

 

 

 

Available with Operating_Data: All,

 

 

 

 

 

System_pressure, Filter_pressure,

 

 

 

 

 

Discharge_temp, Reservoir_temp,

 

 

 

 

 

Motor_current

4.1.3.Timing Parameters

 

Column Title

 

 

Function

 

 

Legal

 

 

 

 

 

 

Values

 

 

 

 

 

 

 

 

 

 

 

 

 

Rate at which data is polled. Note that the

 

 

 

 

Scan_Interval

 

Poll_Delay Connection parameter affects the

 

≥0.1s

 

 

 

 

effective scan interval.

 

 

 