FS-8700-60 Gardner Denver Manual

Page 5 of 11

1.05Client Side Connection Descriptions

 

Section Title

 

 

 

 

Connections

 

 

 

 

Column Title

Function

 

Legal Values

 

 

Specify which port the device

 

P1-P8, R1-R21

 

Port

is connected to the

 

 

 

FieldServer

 

 

 

Protocol

Specify protocol used

 

Gardner_Denver

 

Baud*

Specify baud rate

1200, 9600 (match to Controller)

 

Parity*

Specify parity

 

None

 

Data_Bits*

Specify data bits

7

 

Stop_Bits*

Specify stop bits

1

 

Handshaking*

Specify hardware

 

None

 

handshaking

 

 

Poll_Delay*

Time between internal polls

 

> = 0.2s

 

Timeout*

Time to wait for response

 

> = 0.6s

Example

//Client Side Connections

Connections

 

Port,

Protocol

 

 

P1,

 

Gardner_Denv

 

 

 

er

 

 

 

 

 

1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 7
Image 7
FieldServer instruction manual FS-8700-60 Gardner Denver Manual, None