4.4.7.Map Descriptor Example 4 – Write Day of Week (DOW) or Time
This example illustrates how to write values to an occupancy table. Occupancy tables contain amongst other variables, Day of Week (DOW) settings and time settings. The driver needs to be configured so that it formats these values correctly.
When the DOW write occurs, the driver extracts the value from the Data Array and converts it to a binary string whose bit value is the binary representation of the Data Array value, e.g. DA value = 131 DOW string = 10000011 e.g. DA value = 1 DOW string = 00000001
Occupancy’s are set using a BCD value. Write the value decimal equivalent of 01111100 (62 decimal) to signify an occupancy of Monday to Friday. The bit string starts on Sunday, runs through Monday to Saturday and the final bit is for holidays.
When a time write occurs the driver extracts the value from the Data Array and coverts the value to a time string. The value extracted from the DA is considered to be the number of minutes from midnight, e.g. DA value = 1 - Time = 00:01; DA value = 959 - Time=15:59
Map_Descriptors |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Map_Descriptor_Name, | Scan_interval, | Data_Array_Name, | Data_Array_Offset, | Function, | Node_Name, | Table_Name, | Field_Name , | Length, |
| Data_Type | |||||||
MapDesc13 | , | 1.0s | , | TABLE_OCCPC64S, | 100 | , | wrbx | , | Node_A | , | OCCDEFCS OCCPC64S, | DOW3 | , | 1 |
| , | Occupancy_DOW |
MapDesc14 | , | 1.0s | , | TABLE_OCCPC64S, | 101 | , | wrbx | , | Node_A | , | OCCDEFCS OCCPC64S, | UNOCC3 | , | 1 | , |
| Occupancy_Time |
The Data type tells the driver how to format the value for the write.