FS-8700-82 Carrier DataLink

 

 

 

 

 

 

Page 14 of 31

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

//

Server Side Connections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

 

 

Port,

Baud,

Parity,

Data_bits,

Stop_Bits,

Protocol ,

Handshaking,

Poll_Delay

 

P8,

 

9600,

None ,

8

,

1

,

CarrierDL,

None

,

0.100s

5.2.Server Side Nodes

 

Section

 

 

 

 

 

 

 

 

Title

 

 

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

 

Column

 

 

Function

 

 

Legal Values

 

 

Title

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Up to 32

 

Node_Name

 

Provide name for node

 

alphanumeric

 

 

 

 

 

 

 

characters

 

 

 

 

Modbus station address of physical server node.

 

 

 

 

 

 

 

These correspond to the ‘devices’ configured in the

 

 

 

 

 

 

 

DTPConfig. Thus the Node_ID is not the address of

 

 

 

 

Node_ID

 

the final CCN device.

1-15

 

 

 

 

 

The DataLink DTPConfig table maps a device

 

 

 

 

 

 

 

number (1...15) to a bus number (0-239). Use the

 

 

 

 

 

 

 

Node_ID to tell the driver which device to use.

 

 

 

 

Protocol

 

Specify protocol used

 

CarrierDL

Example

//Server Side Nodes

 

 

 

 

Nodes

 

 

 

Node_Name,

Node_ID,

Protocol ,

Port

FAN1 ,

1 ,

CarrierDL,

 

It is common to leave Server nodes unconnected to a port. This means that the FieldServer can respond with the node’s data irrespective of which port the request is received on.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 14
Image 14
FieldServer instruction manual Server Side Nodes, FS-8700-82 Carrier DataLink Example