FS-8700-82 Carrier DataLink

 

Page 7 of 31

 

Example

 

 

 

 

 

 

 

// Data Arrays

 

 

 

 

 

 

 

Data_Arrays

 

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length

 

DA_AI_01,

UInt16,

200

 

DA_AO_01,

UInt16,

200

 

DA_DI_01,

Bit,

200

 

DA_DO_01,

Bit,

200

4.2.Client Side Connection Descriptions

Section Title

 

 

Connections

 

 

Column Title

Function

Legal Values

Port

Specify which port the device is connected to the

P1-P8, R1-R21

 

FieldServer

 

 

 

300, 600 , 1200,

Baud*

Specify baud rate

2400, 9600 (Vendor

 

 

limitation)

Parity*

Specify parity.

None (Vendor

Limitation)

 

 

Data_Bits*

Specify data bits

8 (Vendor Limitation)

 

 

 

Stop_Bits*

Specify stop bits

1 (Vendor limitation)

 

 

 

Protocol

Specify protocol used

CarrrierDL

 

 

 

Handshaking*

Specify hardware handshaking

None

Poll _Delay*

Time between internal polls

0-32000 seconds, 1

second

 

 

Timeout*

When reading entire tables it is recommended that

0.1 to 60.0 seconds,

the timeout be set to between 15 and 30 seconds.

2.0seconds

 

Additional information is provided in Appendix A.5

 

 

IC_Timeout*

When reading entire tables it is recommended that

 

the ic_timeout be set to approx 15.0 seconds.

 

 

Additional information is provided in Appendix A.5

 

Example

//Client Side Connections

Connections

Port,

Baud,

Parity,

Data_bits,

Stop_Bits,

Protocol,

Handshaking,

Poll_Delay

P8,

9600,

None,

8 ,

1

,

CarrierDL,

None

,

0.100s

1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 7
Image 7
FieldServer Client Side Connection Descriptions, FS-8700-82 Carrier DataLink Example, None, Second, 0seconds