OFFSET

DESCRIPTION

0Number of Read Table messages sent

1Number of Read Variable messages sent

2Number of Write Table messages sent

3Number of Write Var Messages sent

4Number of bytes sent by client driver

5Number of messages sent by client

6Number of response messages received by client

7

Number of times client tries write with alternate format because original method failed

9 Most recent response error

8Number of times client receives an error response

10 Carrier Error: #1 Invalid Command"

11 Carrier Error: #2 Invalid or Non-Existent Table"

12 Carrier Error: #3 Level II communications Error"

13 Carrier Error: #4 Error not defined"

14 Carrier Error: #5 Error not defined"

15 Carrier Error: #6 Device Not Configured"

16 Carrier Error: #7 Variable Does not Exist"

17 Carrier Error: #8 Invalid Data"

18 Carrier Error: #9 Access Restricted"

19 Carrier Error: #10 Limits Exceeded"

20 Carrier Error: #11 Alarms not Available"

21 Carrier Error: #12 Cannot Force Variable"

22 Carrier Error: #13 Parameter Not Found"

23 Carrier Error: #14 Level II Communications NACK"

24 Some other error

25 Number of response bytes received by client

26Number of times client has timeout out waiting for (response) prompt When set then the server sends response whose var names have leading

27spaces. This is used for QAA testing and diagnostic purposes only. Customers should never set this value.

28Number of times client cannot parse / recognize the value sting in a response

29Number of times the server had to store a time greater than 24:00

30Number of times the client sent a message with a time greater than 24:00

31

Number of times the client sent a message to a probable occupancy table

without the correct data types

 