Continued
Mantel and mantel shelf clearances
As with any radiant heat fireplace, the Grand Meridian fireplaces must comply with building code safety clearances, per units that have openings of 6 sq. ft. or greater. For Mantel clearances see Figure 5, page
7.Walls that Adjoin – Safety codes and all practical outlooks insist that your fireplace cannot be installed closer than 2 ft. to any walls in the room the fireplace is housed in or to any walls of adjoining rooms.
Caution in Regards to Combustibles – If any part of the fireplace or objects in the room (curtains, rugs, paint, cushions, etc.) start to show warping or discoloration due to heat from the fireplace, it is time to take immediate action. Do not use the fireplace until you have figured out how to address the problem. You are facing a potential fire hazard. FMI PROD- UCTS, LLC cannot be responsible for the
Hearth Extension
Where the flooring material at the opening of the fireplace is combustible, it is required that the hearth extension be covered with a
If a raised hearth extension is being installed, it must be constructed of
If using a raised hearth or metal base plate, note that a combustible wood header must be no closer than 2" to the top of the dome (see Figure 6, page 8).
Attention: You will note that there will be a gap between the fireplace front and the extension of the
These Grand Meridian Fireplaces have been designed with clearance to combustible floors as indicated in Page 8. Cover any part of the combustible floor system left exposed with 1” (one inch) thick ceramic fiber insulation rated up to 2,100° F.
Attention: It is critical to abide by the clearances listed in this manual for all components specified as it allows for movement of hot air from the fireplace into interior areas of the chimney chase. Also, be certain that the chimney system be installed as stated below. Prior to starting the installation, check with local, regional or state codes for any restrictions or required permits regarding your fireplace installation.
NOTE: It is required that ember protector strips must be laid on the fiber of the
WARNING: Hearth extension is to be installed only as shown in Figure 10.
| Hearth |
Seal Gap | Extension |
Fireplace Front |
|
Ember Protector |
|
Seal Gap |
|
Fireplace Front |
|
Raised Hearth |
|
Ember Protector | Hearth |
| Extension |
| Hearth |
Fireplace Front | Extension |
Elevated |
|
Ember Protector |
|
Figure 10 - Hearth Extension
10 | www.fmiproducts.com |