Continued
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.
Maintain the 2" clearance to combustibles above the dome. DO NOT attach combustible materials on top of the dome.
18" MIN*
H**
8" MIN*
| ||
| facing (not supplied). | |
|
|
|
Condition | Dim. H** |
|
with 6" platform | 10" |
|
with 8" platform | 12" |
|
without platform | 3" |
|
* MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS.
** MEASURED FROM FLOOR TO TOP OF FIREBRICK LINER.
Figure 6: Framing Dimensions for Combustible Floor Systems18" MIN*
½"
MIN**
2" MIN. CLEARANCE TO COMBUSTIBLES AROUND SIDES, REAR AND TOP OF FIREPLACE DOME
**IF METAL FRAMING IS USED MAINTAIN A ½ INCH MIN. AIR SPACE FROM TOP OF LINTEL.
*IF WOOD FRAMING IS UTILIZED IT
MUST BE HELD 18" MIN. FROM TOP OF LINTEL AND 2" MIN.CLEARANCE MUST BE MAINTAINED ALL AROUND FIREPLACE DOME.
Maintain the 2" clearance to combustibles above the dome. DO NOT attach combustible materials on top of the dome.
Model | W |
MM33 | 41” |
MM39 | 47” |
MM44 | 52” |
MM49 | 57” |
MM63 | 71” |
W
8 | www.fmiproducts.com |