WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or instal- lation. All electrical connnections and wiring MUST be installed by a qualified electrician and conform to the National Electrical Code and all local codes which have jurisdiction. Failure to do so can result in personal injury and/or death.

NOTICE

ELECTRIC SHOCK HAZARD

Not following the previous WARNING could result in fire or electrically unsafe conditions which could cause moderate or serious property damage. Read, understand and follow the previous warning.

ELECTRICAL REQUIREMENTS

Wire Size

“Use ONLY time delayed fused disconnect or HACR type circuit breaker as indicated on the unit’s rating plate (see sample on this page). Proper current protection to the unit is the responsibility of the owner”.

Unit MUST

All 208/230v chassis must be hard wired with properly sized breaker. See nameplate for speci￿c chassis electrical requirements. See ￿gure 9 (Page 12) for unit wiring and wall thermostat wiring. See Electrical Rating Table below for wire siz Use HACR type breakers to avoid nuisance trips. All ￿eld wiring must be done in accordance with NEC and local codes.

Electrical Rating Tables

 

 

 

 

15A

14

20A

12

30A

10

Supply voltage

Supply voltage to the unit should be a nominal 208/230 volts. It must be between 197 volts and 253 volts. Supply voltage to the unit should be checked WITH THE UNIT IN OPERATION. Voltage readings outside the specified range can be expected to cause operating problems. Their cause MUST be investigated and corrected.

Sample Nameplate

120524