COOLING ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS
Problem | Possible Cause | Action | |
|
| Replace fuse, reset breaker. If repeats, check | |
| Fuse blown or circuit tripped | fuse or breaker size. Check for shorts in unit | |
|
| wiring & components | |
Unit does not run | Power cord not plugged in | Plug it in | |
System switch in "OFF" position | Set switch correctly | ||
| |||
| Inoperative system switch | Test for continuity in each switch position | |
| Loose or disconnected wiring at switch or other | Check wiring & connections. Reconnect per | |
| components | wiring diagram |
Problem | Possible Cause | Action | |
| Dirty filter | Clean as recommended in Owner's Manual | |
| Restricted airflow | Check for dirty or obstructed coil. Use pressure | |
| wash or biodegradable cleaning agent to clean | ||
|
| ||
Evaporator coil | Inoperative | Test for shorted | |
Short of refrigerant | |||
freezes up | |||
| Inoperative fan motor | Test fan motor & replace if inoperative | |
|
| ||
| Partially restricted capillary tube | across coil. Touch test coil return bends for same | |
|
| temp. Test for low running current |
Problem | Possible Cause | Action | |
| Excessive heat load | Unit undersized. Test cooling performance & | |
| replace with larger unit if needed | ||
|
| ||
| Restriction in line | Check for partially iced coil & check temperature | |
| split across coil | ||
Compressor runs |
| ||
| Check for oil at silver soldered connections. | ||
continually & does |
| ||
Refrigerant leak | Check for partially iced coil. Check split across | ||
not cycle off | |||
| coil. Check for low running amperage | ||
|
| ||
| Check operation of | ||
| remain closed. | ||
|
| ||
| Refer to appropriate wiring diagram |
Problem | Possible Cause | Action | |
|
| Disconnect power to unit. Remove cover of | |
| & check if contacts are stuck. If so, replace | ||
|
| ||
|
|
| |
Turn to higher temp. setting to see if unit cycles | |||
unit off | off | ||
| |||
| Incorrect wiring | Refer to appropriate wiring diagrams | |
| Unit undersized for area to be cooled | Refer to industry standard sizing chart | |
|
|
|
18